Apollo Zone Control Unit 55000-845APO
Açıklama
Apollo Zone Control Unit 55000-845APO
Konvansiyonel yangın dedektör zonlarının adreslenerek bir XP95 çevrimi üzerinden beslenmesini ve izlenmesini sağlamaktadır.
FUNCTION
The XP95 Zone Monitor with Isolator powers and
controls the operation of a zone of up to 20 Orbis/
Series 65 Apollo fi re detectors from the Apollo loop.
FEATURES
The Zone Monitor with Isolator returns a preset
analogue value when all detectors on the zone are in
quiescent state. A different value is returned when a
detector changes to the alarm state. The Zone Monitor
with Isolator latches in the alarm state.
The Zone Monitor with Isolator is fi tted with a
bi-directional short circuit isolator and will be
unaffected by loop short circuits on either the loop
input or loop output.
ELECTRICAL CONSIDERATIONS
The Zone Monitor with Isolator is loop powered and
operates at 17–28V DC with protocol pulses of 5–9V.
PROTOCOL COMPATIBILITY
The Zone Monitor with Isolator operates only with
control equipment using the Apollo XP95 or Discovery
protocol.
MECHANICAL CONSTRUCTION
The Zone Monitor with Isolator is supplied with a
backbox for surface mounting, and is for indoor use
only.